|
|
|
Telecommunication Room Build-out Parameters Installation shall conform with proper practices and codes. (BICSI, ANSI/TIA/EIA, NEC, & local building codes). The standards introduced here are to be considered minimum standards. Any deviations from these standards must be submitted in writing to CNS (cns-projects@berkeley.edu) for written approval by a CNS Project Manager prior to the commencement of construction.LocationTelecommunications Rooms (TR’s) shall be located within 295 cable feet of the most-distant communication outlets they will serve. It is preferable to have TR’s centrally located on a floor and, where possible, to have a single TR serve multiple floors of a building. All TR doors must open onto an easily accessible hallway or space and shall not require passage through any other assignable or otherwise occupied space. No plumbing or mechanicals are to be mounted in or pass through TR’s unless they are specifically needed for the space. TR’s shall be dedicated to communications use only and cannot be shared with departmental storage, janitorial staff, equipment, or other materials. TR’s may not have any windows and must be insulated for noise suppression. To avoid electromagnetic interference, TR placement should avoid adjacencies with motors, X-ray equipment and other electromagnetic generating equipment. The selection of TR locations must be cleared by CNS staff before construction commences. SizeMinimum TR size is 10’x10’. The sizes given below for typical telecommunications rooms are based on the needs of data, voice, and video communication systems. Typically, security, alarm and access control systems can be accommodated in TR’s of these sizes as well.
Area Served by Closet (sq. ft.) Minimum closet size Up to 8,000 10'x 10' 8,000 to 15,000 10'x 12' Greater than 15,000 10'x 14' FlooringFloors shall be sealed concrete at minimum. CeilingIt is preferred TR’s be open to the floor or roof above. If a ceiling must be installed, it should be at a minimum of 10’ from the floor. Entry DoorsDoors must have minimum dimensions of 3”6’ wide by 7’ tall and should swing out of the TR space. There should be no sill installed in the door opening. WallsPlywood BackboardsHardwood three quarter inch, AC, fire retardant, plywood free of defects (knots and voids shall be considered a defect) must be mounted on designated walls of the TR at 0’6” to 8’6” AFF (see CNS for designated walls). Plywood shall be mounted with A side exposed to interior of room and C side against the wall. Plywood shall be mounted so as to be capable of supporting 50 pounds per linear foot of wall space. The plywood shall be painted with white, low-gloss paint leaving the UL fire-rating symbol unpainted and visible. Cable Pathway PenetrationsConduit and/or cable tray penetrations into TR’s shall be as close to the entrance door as is practical. All conduits and cable trays shall be free of burrs and sharp edges. Cut/rough edges shall be covered with plastic/rubber covers. Conduits shall be fitted with smooth bushings. Conduits or sleeves shall protrude into the TR at least 2” from the surface they penetrate, but not more than 4”. All penetrations shall be filled with appropriate fire blocking material to ensure compliance with fire codes. Horizontal PenetrationsHorizontal cable penetrations shall be sized to ensure adequate pathway for anticipated quantity of cables. Penetrations should feed into the appropriate horizontal racking with sufficient support (e.g. waterfalls & ladder racking) to ensure that the cable’s minimum bend-radius specifications are respected. Vertical PenetrationsVertical conduit penetrations shall consist of a minimum of three (3) 4” conduits through the floor with cable support devices in place to support all cables to the appropriate equipment rack or termination area. Where possible, floor penetrations should be made adjacent to the entry door to the TR. Cable SupportAll Horizontal and Vertical cable runs require appropriate support (e.g. Cable Trays, Ladder rack, waterfalls, etc.) that is specifically designed to bear the required cable weight and volume while maintaining bend radius. Changes of elevations greater than 12” require support in the form of dropout waterfalls, else conduits should be long enough to dump directly into the cable tray (minimum 12” above). When additional support is required by a wall, use vertical-mounted ladder rack to carry cables. Media Layout and TerminationCopper Copper cabling shall terminate in 110-type block fields. Field layouts, from left to right when facing the backboard, shall be Data – Riser – Voice. Note that this order depends on room layout and must be verified with CNS before installation. Data, riser, and voice fields shall have room for growth within each field. All cables shall feed into top of 110 towers. All 110 blocks shall be mounted on towers with vertical wire management between towers and at the left and right outsides of each field type. Horizontal cable management devices shall be placed between 100 pair groupings of 110-type blocks and across the tops of the 110 towers to provide for management of patch cords and cross connects. See "Technical Specifications for the Installation of UTP Cabling" (http://cns-oir.berkeley.edu/standards/UTP_Specs.shtml) for specific copper cable termination practices and materials.) Fiber Coils of spare fiber shall be mounted on walls high above the uppermost horizontal racking. Fiber Centers shall be rack mounted. See "Technical Specifications for the Installation of Fiber Optic Cable" (http://cns-oir.berkeley.edu/standards/fiber.shtml) for specific fiber cable termination practices and materials. RackingHorizontalTR layouts shall include 3 layers of overhead horizontal cable ladder racking. All cable racking shall be ladder type. Ladders must have radiused downturns (ie: waterfalls) at each point where cables transition from horizontal to vertical.
Uppermost horizontal layerThe uppermost layer should be mounted minimum 8’6” above the floor. It shall be used for the routing and support of horizontal station cabling, incoming copper, and fiber riser cable.
Middle horizontal layerThe middle layer shall be mounted 7’6” above the floor and shall be 4”x4” fiber trough for the routing and support of fiber patch cables run from above the Fiber Centers to equipment mounted in the vertical racks. Fiber trough shall include downspouts leading to 2”x2” vertical cable management on each of the equipment racks.
Lowest horizontal layerThe lowest layer of cable support tray shall be mounted 7’ above the floor and be used for the routing and support of copper patch cables from the 110 fields to the rack-mounted TR electronics. The lowest ladder rack shall be bolted to the tops of the vertical racks below. They shall be mounted 6” off the wall above the 110 field. All cable racking shall be ladder type.
Equipment RacksVertical equipment racks shall be 19” UL Listed Chastworth racks. Minimum horizontal separation between rows of racks shall be 6 feet. Minimum distance from the “back” of a rack to a wall shall be 5 feet. All racks shall be securely bolted to the floor of the TR If mounted on raised flooring, racking shall be centered on floor tiles to allow under floor access from both front and rear of the rack. Where raised-flooring exists, racks shall be bolted to the sub-floor beneath the panels of the raised-floor. All racks shall have adequate earthquake bracing to the walls and/or ceiling. Seismic gusset kits and dust cover shall be installed on all racks.
Equipment Rack LabelingEquipment racks shall be clearly labeled with unique 2-digit serial number reset to 01 for each TR. Numbering of racks shall start with rack at furthest wall and increment working towards the door. The label shall consist of machine Printed Numbers minimum 2 inches high.
Cable ManagementDouble sided vertical wire management must be mounted on both sides of each
vertical rack. Racks mounted side-by-side should have a minimum of 10” wide
vertical manager between them and 6” wide vertical managers on each end
of a row of racks. Within the front of the vertical manager there should be
a vertical 2” x 2” fingered fiber duct (with cover) and 2” x
4” downspout transition with cover. Within the rear of the vertical manager
there should be two (2) APC metered 20A PDU power strips. Power
TR’s shall be fed via the StarLine Track Bus System (http://www.uecorp.com/power-distribution.asp).
Electrical requirements: Voltage-120/220V or 300V, Frequency-60 Hz, Ampacity-60A,
Conductors-Qty. 4 (Phase A, B, C, and Neutral), Grounding-Aluminum Housing. GroundingIt is expected that each TR shall have EnvironmentalLightingSufficient lighting shall be provided to ensure a minimum of 50 foot candles, measured 3’ above the finished floor after all racks, cable trays and cables are in place. A light switch shall control TR lights only and be placed near the entrance door. HVACSufficient HVAC shall be included in the design of the TR to maintain temperatures at 64 to 75 degrees Fahrenheit at 30% to 55% relative humidity. The TR must be provisioned for continuous HVAC (24 hours per day and 365 days per year) with local control. A positive pressure shall be maintained with a minimum of one air change per hour, or as required by applicable code. HVAC shall be provided according to the following table:
Number BTU/Hr BTU/Hr Tons of HVAC of Racks (max) (de-rated) (max rounded down) 1 6,500 4,875 1/2 ton 2 13,000 9,750 1 ton 3 19,500 14,625 1 1/2 ton These figures are derived as follows: Each rack has two power strips. Each power strip is a separate 20A circuit. Each circuit is de-rated at the breaker to 16A.
3840 watts X 3.4 = 13,056 BTU/Hr per rack 1 ton = 12,000 BTU/Hr Fire ProtectionFire protection must be provided to meet campus fire code. In order of preference: Preaction Fire sprinkler system, drainage trough below sprinkler pipes. Wire mesh cages must be installed over all sprinkler heads.
KeyingAll TR door locks shall be keyed with one of the following, in order of preference: Proximity card-key system run by the campus police department, Cyber core, T-Key.
TelephoneThe MDF/BDF TR in each building shall have a wall telephone installed. The handset cord shall be of sufficient length to reach any point within the TR. TR phones shall be restricted to campus-only calls.
LabelsAll cables, fiber centers, 110 blocks, and equipment must be labeled with machine made, permanent labels according to current labeling standards.
SignageThe outside of each TR needs to have a sign indicating the room number. The sign must not indicate that it is a TR. Installation shall conform with proper practices and codes. (BICSI, ANSI/TIA/EIA, NEC, & local building codes). The standards introduced here are to be considered minimum standards. Any deviations from these standards must be submitted in writing to CNS (cns-projects@berkeley.edu) for written approval by a CNS Project Manager prior to the commencement of construction. Version 2.3 Updated 8/1/2006 Send comments to msawyer@socrates.berkeley.edu
Internal |
|
OIR Home | CNS Home | UCB Home | CNS Search | Request Services |